QJ1-50氣體(瓦斯)繼電器
差壓控制器:JC3.5 0.05-0.35MPA差壓控制器、JC3.5FS差壓控制器、CWK-22 0.1-0.4MPA差壓控制器、CWK-11 0.1-0.5MPA差壓控制器、JC0535 0.05-0.35MPA差壓控制器、JY616 0.6-1.6MPA差壓控制器、YWK-22差壓控制器、D520/7DD差壓控制器 D520/7DDK差壓控制器
溫度控制器:D530/7DD溫度控制器 D530/7DDK溫度控制器、D540/7T溫度控制器 D540/7TK溫度控制器、D541/7T溫度控制器
溫度繼電器:XU-200溫度繼電器、JW2溫度繼電器、JW4溫度繼電器、JVC-1M溫度繼電器、JVC-3M溫度繼電器
壓力傳感器:CY1壓力傳感器、CYO壓力傳感器
氣體繼電器:QJ1-80氣體繼電器、QJ1-50氣體繼電器、QJ4-50氣體繼電器、QJ4-80氣體繼電器
油流繼電器:YJ-50油流繼電器、YJ-80油流繼電器、YJ-150油流繼電器
速度繼電器:JY-1 2A/500V速度繼電器
QJ2-40型氣體繼電器 1. 用途 The use
QJ2-40型氣體繼電器主要用于保護各種類型的油浸式全密封變壓器的安全運行。必要時將變壓器從電網(wǎng)中切除。
A gas relay in QJ2-40 is mainly used for protection of safe running of various types of oil-immersed fully sealed transformer. If necessary, the transformer will be cut off from the power grid.
2. 型號及其含義 The model and its meanings
本產品的型號及其所代表的意義如下:
The model and its meanings of the product are following:
3. 氣體繼電器的結構及其工作原理 The structure and the work principle of the gas relay
3.1 氣體繼電器外部結構如圖所示:The outer structure of the gas relay is following:
內部由浮子及兩個干簧接點構成,接點閉合將報警信號或切除信號通過接線端子輸出。
The inner is composed of float and two spring contacts and the contact closing makes alarm signal or cutting signal output by the connection terminal.
3.2 氣體繼電器的工作原理 The work principle of the gas relay
當變壓器內部出現(xiàn)故障,變壓器油分解而產生氣體或溫度下降而少油,此時氣體聚集在繼電器的氣室內,迫使油面下降,浮子隨油面下降,當油面下降到一定程度時,首先報警信號接點接通,發(fā)出報警信號。若油面繼續(xù)下降,到一定程度時,切除信號接點接通,發(fā)出切除信號,將變壓器從電網(wǎng)中切除,從而達到保護變壓器的目的。
When the fault takes place inside of the transformer, the transformer oil is decomposed to produce o gas or make the temperature drop to result to less oil. At this time, the gas is gathered in the gas interior of the relay to force the oil level to drop and the float will drop with the oil level. When the oil level is dropped to a certain degree, the alarm signal contact is connected to send the alarm signal out at first. If the oil level continually drops to some degree, the cutting signal contact is connected to send the cutting signal out to cut the transformer off from the power grid to reach at the purpose of the protection of the transformers.
4. 主要技術參數(shù) The main technical parameters
4.1 工作溫度 The work temperature:-30℃~ +90℃
4.2 管路通徑 The pipeline path diameter:Φ40mm
4.3 密封試驗壓力 The seal test pressure:0.2MPa 20min
4.4 接線端子對地 The earth terminal blocks:AC 2KV 1min
4.5 接點容量 The contact capacity: DC/AC 220V 0.3A
4.6 動作特性 The action characteristic:
當油面下降到箱蓋下35mm處,發(fā)出報警信號。
When oil dropped to 35mm under the cover, send an alarming signal out.
當油面下降到箱蓋下50mm處,發(fā)出切除信號。
When oil dropped to 50mm under the cover, send a cutting signal out.
5. 安裝尺寸 The installation size
QJ2-40型氣體繼電器的結構及安裝尺寸
The structure and the installation size of gas relay in QJ2-40
6. 使用及維護 The use and the maintenance
6.1 產品出廠前,已經(jīng)過調試和密封試驗,無特殊情況下不要隨意拆卸,以免影響產品的準確度和密封性能。
Before the products leave the factory, they have been adjusted and test. In common case, they should not been disassembled arbitrarily, so as not to affect the accuracy and the sealing performance of the products.
6.2 為方便氣體繼電器進行現(xiàn)場檢修,其安裝位置應保證氣體繼電器芯體能從殼體中取出。
In order to help the repair of the gas relay in site, its installation location should ensure the core body of the gas relay to be able to be removed from the shell.
6.3 氣體繼電器必須安裝在變壓器油箱箱蓋上,便于收集氣體。安裝法蘭和密封墊由繼電器生產廠提。
The gas relay must be installed on the tank cover of the transformer to facilitate the collection of gas. The installed flanges and the seal gaskets will be provided by the relay manufacturer.
6.4 放氣及收集氣樣:將放氣閥上的防塵蓋擰下,旋動內部的小六角氣閥即可放氣。若在放氣嘴上接一內徑Φ6的膠管,即可收集氣樣。
The Deflation and collecting gas samples: Turn the dust cover on the releasing valve off and turning the small inner hex valve can release gas. If connect a hose with Φ6 diameter to the releasing nozzle, it can collect the gas sample.
6.5 電氣接線:1、2端子接報警信號,3、4端子接切除信號(見A向圖)。
The electrical wiring:Terminal 1, 2 for alarming signals; Terminal 3, 4 for cutting signals (see diagram A)
6.6 安裝時不得將浮子外保護罩去掉.
When installation, the outer protection cover of the float can not be removed.
7. 投運前測試 The test before put into operation
投入運行前,利用氣體繼電器頂蓋上的探針可進行動作特性的測試。先擰下探針頂上的防塵蓋,緩慢按下探針,將依次發(fā)出報警信號和切除信號。如不能發(fā)出信號,請檢查接線是否正確,若確認接線正確仍不能發(fā)出信號,請立即與我公司,我公司將迅速予以解決。
Before put into operation, use the probe on the cap of the gas relay can carry out the test of the action characteristic. At first, turn off the duct cap on the probe and press the probe down slowly, it will send alarm signals and cutting signals out I order. If it can not send a signal out, check if the wiring is correct. If The wiring is confirmed to correct and it still can not send the signal out, please do not hesitate to contact our company, my company will be resolved quickly.
|